beautypg.com

Configuration 39, Out.3 – West Control Solutions N8800 User Manual

Page 39

background image

Configuration level

8800 process controller

39

Configuration parameters

Out.3

Name

Value range Description

Default

O.tYP

Signal type selection OUT3

0

0

relay / logic (only visible with current/logic voltage)

1

0 ... 20 mA continuous (only visible with

current/logic/voltage)

2

4 ... 20 mA continuous (only visible with

current/logic/voltage)

3

0...10 V continuous (only visible with current/logic/voltage)

4

2...10 V continuous (only visible with current/logic/voltage)

5

transmitter supply (only visible without OPTION)

O.Act

Method of operation of output OUT3 (only visible when

O.TYP=0)

1

0

direct / normally open

1

inverse / normally closed

Y.1

Controller output Y1 (only visible when O.TYP=0)

0

0

not active

1

active

Y.2

Controller output Y2 (only visible when O.TYP=0)

0

0

not active

1

active

Lim.1

Limit 1 signal (only visible when O.TYP=0)

1

0

not active

1

active

Lim.2

Limit 2 signal (only visible when O.TYP=0)

0

0

not active

1

active

Lim.3

Limit 3 signal (only visible when O.TYP=0)

0

0

not active

1

active

dAc.A

Valve monitoring (DAC) (only visible when O.TYP=0)

0

0

not active

1

active

LP.AL

Interruption alarm signal (LOOP) (only visible when

O.TYP=0)

0

0

not active

1

active

HC.AL

Heating current alarm signal (only visible when O.TYP=0)

0

0

not active

1

active

HC.SC

Solid state relay (SSR) short circuit signal (only visible

when O.TYP=0)

0

0

not active

1

active