West Control Solutions N8800 User Manual
Page 43

Configuration level
8800 process controller
43
Configuration parameters
Name
Value range Description
Default
SP.E
Switching to external setpoint SP.E
0
0
no function (switch-over via interface is possible)
1
always active
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
Y2
Y/Y2 switching
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
6
Ò - key switches
Y.E
Switching to fixed control output Y.E
0
0
no function (switch-over via interface is possible)
1
always activated (manual station)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
6
Ò - key switches
mAn
Automatic/manual switching
0
0
no function (switch-over via interface is possible)
1
always activated (manual station)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
6
Ò - key switches
C.oFF
Switching off the controller
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
6
Ò - key switches
m.Loc
Blockage of hand function
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches