3.6 Manual self-tuning

The optimization aid can be used with units on which the control parameters shall

be set without self-tuning.

For this, the response of process variable x after a step change of correcting

variable y can be used. Frequently, plotting the complete response curve (0 to

100%) is not possible, because the process must be kept within defined limits.

Values T

g

and x

max

(step change from 0 to 100 %) or ∆t and ∆x (partial step

response) can be used to determine the maximum rate of increase v

max

.

y

= correcting variable

Y

h

= control range

Tu

= delay time (s)

Tg

= recovery time (s)

X

max

= maximum process value

V

max

= Xmax

Tg

= ∆

x

t

= max. rate of increase of process value

The control parameters can be determined from the values calculated for delay

time T

u

, maximum rate of increase v

max

, control range X

h

and characteristic K

according to the formulas given below. Increase Pb1, if line-out to the set-point

oscillates.

Operation

Manual self-tuning

24

8800 process controller

Tu

Tg

t

x

y

100%

0%

t

Yh

Xmax

{X

{t