D.1.3, Range, D.1.4 – Spectrex 40/40UFL Ultra Fast UV/IR User Manual
Page 71: Charging the battery, Table 25: sensitivity ranges, D.1.3 range, D.1.4 charging the battery
TM 40/40UFL, Rev (2) August 2013
Long Range UV/IR Fire Simulator
59
D.1.3 Range
Table 25: Sensitivity Ranges
Detector
Model
Standard Test
Range(ft./m)
Extended Test Range
with collimator
(ft./m)
40/40UFL
14.5/4.5
29/9
Notes:
The minimum distance from the detector is 20 inches (50 cm).
The optional beam collimator is fitted for Extended Range.
At extreme temperatures, there is a 15% maximum reduction in the
range.
Important: Keep the Fire Simulator in a safe place when not in use.
D.1.4 Charging the Battery
The Fire Simulator uses NiCd batteries as a rechargeable power source.
When the batteries are fully charged, the simulator operates for at least
60 times without recharging. An internal buzzer is sounded when the
voltage from the batteries is lower than the required operational level.
➣
To charge the battery:
1
Place the Fire Simulator on a table in a safe area.
2
Turn the sealed plug (next to the operation button) counter-clockwise
with a suitable wrench.
3
Connect the battery charger.
4
Charge for a maximum of 14 hours.
5
Disconnect the charger.
6
Tighten the sealed plug clockwise.