beautypg.com

Table 1: wiring options – Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 15

background image

TM 40/40UFL, Rev (2) August 2013

Model and Types

3

Table 1: Wiring Options

Wiring
Option

Connections Provided

1

Power

Analog
Output

Fault

Relay

N.C.

Alarm

Relay

N.O.

0-20mA

Sink

RS-485

-

2

Power

Analog
Output

Fault

Relay

N.C.

Alarm

Relay

N.O.,

N.C.

0-20mA

Source RS-485 HART

3

Power

Analog
Output

Fault

Relay

N.O.

Alarm

Relay

N.O.,

N.C.

0-20mA

Source

RS-485 HART

4

Power

Analog
Output

Fault

Relay

N.C.

Alarm

Relay

N.O.

Auxiliary

N.O.

RS-485

-

5

Power

Analog
Output

Fault

Relay

N.O.

Alarm

Relay

N.O.

Auxiliary

N.O.

RS-485

-

Note: Wiring option 1 is default. The mA 'Sink' output can be altered to
'Source' type, with a link between terminals 1 and 8. No other wiring options
can be changed on site.

For example, product number 40/40UFL-321SC has the following options:

Wiring Option: 3 (Power, Manual BIT, RS-485, 0-20mA (Source) with
the HART protocol, Fault Relay (N.O.), Alarm Relay (N.O., N.C.))

Temperature Range: 2 (85°C)

Cable Entry: 1 (M25)

Housing : S (Stainless Steel)

Approval: C (ATEX, IECEx)

Note: Check your specific part numbers against the information in Checking
the Product Type
on page 20.