2 built-in-test (bit), 1 how the bit operates, Built-in-test (bit) – Spectrex 40/40UFL Ultra Fast UV/IR User Manual
Page 28
SharpEye
TM
Ultra Fast UV/IR Flame Detector User Guide
16
Internal Detector Tests
Processor Watch dog
Software
Memory
Oscillator frequency
Response to Fault Indication
If a failure is found, the detector indicates by:
Fault relay:
Opens in wiring option 1, 2, and 4
Closes in wiring option 3 and 5
0-20mA: indicates Fault (0mA or 2mA) in wiring option 1, 2, 3
LED – Yellow flashes (4 Hz)
Correcting the Fault
The fault indications remain until the detector’s power is removed. The fault
indications return if the fault is still found when power is restored.
1.6.2 Built-In-Test (BIT)
The detector’s Built-In-Test (BIT) also checks the following:
Electronics circuitry
Sensors
Window cleanliness
The detector can be set to perform the BIT automatically.
1.6.2.1 How the BIT Operates
The detector's status remains unchanged if the result of a BIT is the
same as the current status (NORMAL or BIT Fault)
the detectors’ status is changed (from Normal to BIT Fault or vice versa)
if the BIT differs from the current status
Note: In ‘BIT Fault’ status the detector can continue to detect a fire.