2 automatic bit, Table 8: results of a successful bit, Table 9: results of an unsuccessful bit – Spectrex 40/40UFL Ultra Fast UV/IR User Manual
Page 29
TM 40/40UFL, Rev (2) August 2013
Internal Detector Tests
17
1.6.2.2 Automatic BIT
The detector automatically performs a BIT every 15 minutes. A successful
BIT sequence does not activate any indicator.
All outputs of BIT results function as described in Table 8 and Table 9, and
the BIT is automatically executed every 1 minute. This continues until a
successful BIT occurs, when the detector resumes normal operation.
Table 8: Results of a Successful BIT
Output
Result
Fault relay
Wiring options 1, 2, 4: remains CLOSED
Wiring options 3 and 5: remains OPEN
0-20mA
output
Wiring option 1, 2, 3: Normal (4 mA)
Power LED
Green, Flashing, 1 Hz On (Normal)
Table 9: Results of an Unsuccessful BIT
Output
Result
Fault relay
Wiring option 1, 2, 4: changes to Open
Wiring option 3 and 5: changes to Closed
0-20mA output Wiring option 1, 2, 3: BIT Fault (2mA)
Power LED
Yellow, Flashing, 4 Hz
BIT procedure
Performed every 1 minute