Table 23: wiring length in feet (meter), Table 23 – Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 62

background image

SharpEye

TM

Ultra Fast UV/IR Flame Detector User Guide

50

General Instructions for Electrical Wiring

Table 23: Wiring length in feet (meter)

Number

of

Detectors

Recommended Wire Diameter (AWG)

Power

Supply

Range

(VDC)

24

18

16

14

-

-

22-32

20

18

16

14

-

-

22-32

16

20

18

16

14

-

22-32

12

20

18

16

14

-

20-32

8

20

18

16

14

-

20-32

4 and less

20

18

16

16

14

20-32

Ft (m)

164

(50)

328

(100)

492

(150)

656

(200)

820

(240)

Max. Length from Power Supply to Last

Detector

Calculation Formula

Use the following formula to calculate minimum wire gauge per wire length
between the power supply (controller) and the detector, considering the
number of detectors on the same power line, where:

L = Actual wire length between the detector and the power supply.

N = Number of detectors per loop.

R = Resistance of wire per 100 m (see Table 23).

V = Voltage drop on the wire.

Calculate the voltage drop on the wire as follows:

V = 2L x R x N x 0.2A

100

20+V = Minimum required voltage of the power supply

0.2A is the maximum power consumption of the detector

For example,

If N=1 (1 detector in loop)

L=1000m

Wire size = 1.5mm² (see Table 22, the resistance per 100m for 1.5mm² is
1.4Ω)

You calculate the voltage drop in the wire as follows:

2 x 1000 x 1.4Ω x 1 x 0.2A = 5.6V

100

The minimum voltage of the power supply should be 20V + 5.6V = 25.6V