beautypg.com

Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 58

background image

SharpEye

TM

Ultra Fast UV/IR Flame Detector User Guide

46

Outputs

Analog Output
The Analog Output is used for fast detection signal

20 msec. It provides 0 V at Normal and 5 V at Alarm.

HART Protocol
The HART protocol is a digital communication signal at
a low level on top of the 0-20mA. This is a bi-
directional field communication protocol used to
communicate between intelligent field instruments
and the host system. HART is available in wiring
options 2 and 3.
Through the HART protocol the detector can:

Display set-up

Reconfigure the set-up

Display detector status and definition

Perform detector diagnostics

Troubleshoot

For more details refer to HART Manual TM777030.

Communication Network: The detector is equipped
with an RS-485 communication link that can be used
in installations with computerized controllers.
The communications protocol is Modbus compatible.

This protocol is a standard and widely used.

It enables continuous communication between a
standard Modbus controller (Master device) and a

serial Network of up to 247 detectors.

Heated
Optics

The front window can be heated to improve performance
in icing, condensation and snow conditions. The heater
increases the temperature of the optical surface by 5-8°F
(3-5°C) above the ambient temperature. The heated

optics can be configured in three ways:

Off: The optics are not heated

On: The optics are heated continuously

Auto: Operated only when the change of temperature

requires the heating. (default)

In Auto mode the start heating temperature can be
defined between 32°F - 122°F (0°C - 50°C). The detector
stops heating the window when the temperature is 27°F
(15°C) above the start temperature.