beautypg.com

5 installation cables, 1 conduit installation, Installation cables – Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 35: Conduit installation

background image

TM 40/40UFL, Rev (2) August 2013

Installation Cables

23

2.5

Installation Cables

Follow the following guideline for the cable installation:

All cables to the detector must be well shielded in order to comply with
EMC requirement (see Technical Specifications on page 60).

Ground the detector to the nearest ground point (not more than 3m
from the detector location).

Install the detector with the cable entries placed downwards.

2.5.1 Conduit Installation

The conduit used for the cabling must comply with the following:

To avoid water condensation water in the detector, install the detector
with the conduits placed downward, that include drain holes.

When using the optional tilt mount, use flexible conduits for the last
portion connecting to the detector.

For installations in atmospheres as defined in group B of the NFPA 72E,
seal the conduits inlets.

When pulling the cables through the conduits, ensure that they are not
tangled or stressed. Extend the cables about 30 cm. (12 in.) beyond the
detector location to accommodate wiring after installation.

After the conductor cables have been pulled through the conduits,
perform a continuity test.