beautypg.com

Table 19: contact ratings, Table 20: 20 ma current output – Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 57

background image

TM 40/40UFL, Rev (2) August 2013

Outputs

45

Option 2: Power, RS-485, 0-20mA (Source) and
HART protocol, Analog Output, Fault Relay (N.O),
Alarm Relay, (N.O), (N.C).

Option 3: Power, RS-485, 0-20mA (Source) and
HART protocol, Analog Output, Fault Relay (N.O),

Alarm Relay (N.O, N.C).

Option 4: Power, RS-485, Analog Output, Fault Relay

(N.C), Auxiliary Relay (N.O), Alarm Relay, (N.O).

Option 5: Power, RS-485, Analog Output, Fault Relay
(N.O), Auxiliary Relay (N.O), Alarm Relay, (N.O).

Electrical
Outputs

Dry Contact Relays

Table 19: Contact Ratings

Relay
Name

Type

Normal
Position

Maximum
Ratings

Alarm

SPDT

N.O., N.C.

2A at 30 VDC

Auxiliary

SPST

N.O.

2A at 30 VDC

Fault
(see Notes

1 and 2)

SPST

N.C. or
N.O

2A at 30 VDC

Notes:
1. The Fault relay (in wiring options 1, 2, 4) is

normally energized closed during normal operation
of the detector. The relay is de-energized open if a

fault condition or low voltage situation occurs.

2. In wiring options 3, 5 the relay is normally

energized open during normal operation of the
detector. The relay is de-energized close contact if

a fault condition or low voltage situation occurs.

0-20mA Current Output: The 0-20mA can be Sink
or Source according to the wiring option source (see
General Instructions for Electrical Wiring on page 49).

The maximum permitted load resistance is 600Ω.

Table 20: 20 mA Current Output

State

Output

Fault

0 +1 mA

BIT Fault

2 mA ±10%

Normal

4 mA ±10%

IR

8 mA ±5%

UV

12 mA ±5%

Warning

16 mA ±5%

Alarm

20 mA ±5%