Table 19: contact ratings, Table 20: 20 ma current output – Spectrex 40/40UFL Ultra Fast UV/IR User Manual
Page 57
TM 40/40UFL, Rev (2) August 2013
Outputs
45
Option 2: Power, RS-485, 0-20mA (Source) and
HART protocol, Analog Output, Fault Relay (N.O),
Alarm Relay, (N.O), (N.C).
Option 3: Power, RS-485, 0-20mA (Source) and
HART protocol, Analog Output, Fault Relay (N.O),
Alarm Relay (N.O, N.C).
Option 4: Power, RS-485, Analog Output, Fault Relay
(N.C), Auxiliary Relay (N.O), Alarm Relay, (N.O).
Option 5: Power, RS-485, Analog Output, Fault Relay
(N.O), Auxiliary Relay (N.O), Alarm Relay, (N.O).
Electrical
Outputs
Dry Contact Relays
Table 19: Contact Ratings
Relay
Name
Type
Normal
Position
Maximum
Ratings
Alarm
SPDT
N.O., N.C.
2A at 30 VDC
Auxiliary
SPST
N.O.
2A at 30 VDC
Fault
(see Notes
1 and 2)
SPST
N.C. or
N.O
2A at 30 VDC
Notes:
1. The Fault relay (in wiring options 1, 2, 4) is
normally energized closed during normal operation
of the detector. The relay is de-energized open if a
fault condition or low voltage situation occurs.
2. In wiring options 3, 5 the relay is normally
energized open during normal operation of the
detector. The relay is de-energized close contact if
a fault condition or low voltage situation occurs.
0-20mA Current Output: The 0-20mA can be Sink
or Source according to the wiring option source (see
General Instructions for Electrical Wiring on page 49).
The maximum permitted load resistance is 600Ω.
Table 20: 20 mA Current Output
State
Output
Fault
0 +1 mA
BIT Fault
2 mA ±10%
Normal
4 mA ±10%
IR
8 mA ±5%
UV
12 mA ±5%
Warning
16 mA ±5%
Alarm
20 mA ±5%