Table 24: wiring connections – Spectrex 40/40UFL Ultra Fast UV/IR User Manual
Page 64
SharpEye
TM
Ultra Fast UV/IR Flame Detector User Guide
52
Typical Wiring Configurations
Table 24: Wiring Connections
Wiring
Option
Detector
Model
Terminals
3
5
8
9
1
40/40L, LB,
L4, L4B-
1XXXX
Analog
Output
Fault Relay
(N.C)
0-20mA
(Sink)
0-20mA
(Sink)
2
40/40L, LB,
L4, L4B-
2XXXX
Analog
Output
Fault Relay
(N.C)
Alarm
Relay
(N.C)
0-20mA
Source
3
40/40L, LB,
L4, L4B-
3XXXX
Analog
Output
Fault Relay
(N.O)
Alarm
Relay
(N.C)
0-20mA
Source
4
40/40L, LB,
L4, L4B-
4XXXX
Analog
Output
Fault Relay
(N.C)
Auxiliary
Relay
(N.O)
Auxiliary
Relay N.O.
5
40/40L, LB,
L4, L4B-
5XXXX
Analog
Output
Fault Relay
(N.O)
Auxiliary
Relay
(N.O)
Auxiliary
Relay N.O.
Figure 9: Typical Wiring for 4 Wire Controllers (Using Option 1 or 2
Wiring)