beautypg.com

A specifications, Specifications, Technical specifications – Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 55: Aspecifications, A.1 technical specifications

background image

Technical Specifications

43

A

Specifications

In this appendix…

Technical Specifications

page 43

Electrical Specifications

page 44

Outputs

page 44

Approvals

page 47

Mechanical Specifications

page 47

Environmental Specifications

page 47

A.1

Technical Specifications

Spectral Response

40/40UFL UV:0.185 – 0.260µm IR:2.5 - 3.0µm

Detection Range

(at highest Sensitivity
Setting for 1ft

2

(0.1m

2

) pan

fire)

Fuel

ft. / m

Fuel

ft. / m

n-Heptane

65 / 20

Kerosene

42 / 14

Gasoline

65 / 20

Ethanol 95%

23 / 7

Diesel Fuel

40 / 13.5

Methanol

26 / 8

JP5

42 / 14

IPA (Isopropyl
Alcohol)

43 / 13

Methane*

16 / 5

Polypropylene
Pellets

16 / 5

LPG*

16 / 5

Ammonia* 16 / 5

Hydrogen*

23 / 7

Silane* 20 / 6

Office Paper

16 / 5

* 20" (0.5m) high, 8" (0.2m) width plume fire

Response Time

Typically 3 seconds

.

High speed 20 msec response to

Flash fire

Adjustable Time Delay Up to 30 seconds
Sensitivity Ranges

1 ft

2

(0.1m

2

) n-heptane pan fire from 65 ft. (20 m)

Fields of View

Horizontal 100

, Vertical 90

Built-In-Test (BIT)

Automatic (only)