A specifications, Specifications, Technical specifications – Spectrex 40/40UFL Ultra Fast UV/IR User Manual
Page 55: Aspecifications, A.1 technical specifications
Technical Specifications
43
A
Specifications
➣ In this appendix…
page 43
page 44
page 44
page 47
page 47
page 47
A.1
Technical Specifications
Spectral Response
40/40UFL UV:0.185 – 0.260µm IR:2.5 - 3.0µm
Detection Range
(at highest Sensitivity
Setting for 1ft
2
(0.1m
2
) pan
fire)
Fuel
ft. / m
Fuel
ft. / m
n-Heptane
65 / 20
Kerosene
42 / 14
Gasoline
65 / 20
Ethanol 95%
23 / 7
Diesel Fuel
40 / 13.5
Methanol
26 / 8
JP5
42 / 14
IPA (Isopropyl
Alcohol)
43 / 13
Methane*
16 / 5
Polypropylene
Pellets
16 / 5
LPG*
16 / 5
Ammonia* 16 / 5
Hydrogen*
23 / 7
Silane* 20 / 6
Office Paper
16 / 5
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time
Typically 3 seconds
.
High speed 20 msec response to
Flash fire
Adjustable Time Delay Up to 30 seconds
Sensitivity Ranges
1 ft
2
(0.1m
2
) n-heptane pan fire from 65 ft. (20 m)
Fields of View
Horizontal 100
, Vertical 90
Built-In-Test (BIT)
Automatic (only)