1 verifying the detector wiring, Verifying the detector wiring, Table 13: model 40/40ufl wiring options – Spectrex 40/40UFL Ultra Fast UV/IR User Manual
Page 40
SharpEye
TM
Ultra Fast UV/IR Flame Detector User Guide
28
Connecting the Detector
7
Verify the wiring. Improper wiring may damage the detector.
8
Check the wires for secure mechanical connection and press them neatly
against the terminal to prevent them from interfering while closing the
back cover (figure 7).
9
Place and secure the detector’s back cover by screwing the three (3)
socket-head-screws in the Cover Bolts (Figure 4).
2.7.1 Verifying the Detector Wiring
The detector has five output wiring options within the Exde integral terminal
section of the enclosure. There are 12 terminals labeled 1-12.
Table 13 describes the function of each terminal for all the wiring options.
Table 13: Model 40/40UFL Wiring Options
Wire
Terminal
No.
Option 1
Default
Option 2
Option 3
Option 4
Option 5
1
+24 VDC
+24 VDC
+24 VDC
+24 VDC
+24 VDC
2
0 VDC
0 VDC
0 VDC
0 VDC
0 VDC
3
Analog
Output
Analog
Output
Analog
Output
Analog
Output
Analog
Output
4
Fault
Relay N.C.
Fault
Relay N.C.
Fault
Relay N.O.
Fault
Relay N.C.
Fault
Relay N.O.
5
6
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
7
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
8
0-20mA
In
Alarm
Relay N.C.
Alarm
Relay N.C.
Auxiliary
N.O.
Auxiliary
N.O.
9
0-20mA
Out
0-20mA
Out*
0-20mA
Out*
Auxiliary C Auxiliary C
10
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
11
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
12
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
*Available with the HART protocol.
Notes:
RS-485 is used for communication network as specified in Appendix C
(Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for
configuration/diagnostics.
Alarm relay:
N.O. energized contact in wiring options 1, 4, 5.