beautypg.com

3 hart protocol, 4 rs-485 modbus, 5 product certification – Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 18: 1 atex, iecex, Hart protocol, Rs-485 modbus, Product certification

background image

SharpEye

TM

Ultra Fast UV/IR Flame Detector User Guide

6

Principles of Operation

1.4.3 HART Protocol

The 40/40 Flame Detectors use the HART protocol.

HART Communication is a bi-directional industrial field communication
protocol used to communicate between intelligent field instruments and host
systems. HART is the global standard for smart process instrumentation and
the majority of smart field devices installed in plants worldwide are HART-
enabled. HART is available in wiring options 2 and 3, see Table 1, page 3.

HART technology is easy to use and very reliable.

Through the HART connection, you are able to perform:

Detector set-up

Detector troubleshooting

Detector health and status

For more details, refer to the HART Manual TM 777030.

1.4.4 RS-485 Modbus

For more advanced communications, the 40/40UFL detector has an RS-485
Modbus-compatible output that provides data communication from a
network (up to 247 detectors) to a host computer or universal controller for
central monitoring. This feature allows for reduced installation costs, easy
maintenance and local or remote diagnostic tools.

1.4.5 Product Certification

The 40/40UFL Flame Detectors have the following certifications:

ATEX, IECEx, page 6

FM, page 7

SIL-2 Approved (TÜV) , page 7

EN54-10, page 7

1.4.5.1 ATEX, IECEx

The 40/40UFL Flame Detector is certified to:

ATEX Ex II 2 GD per SIRA 07ATEX1250 and IECEx SIR. 07.0085

Ex de IIC T5 Ta -55°C to +75°C

Ex tD A21 IP66/X7 T95°C

Ex de IIC T4 Ta -55°C to +85°C

Ex tD A21 IP66/X7 T105°C

This product is suitable to use in hazardous zones 1 and 2 with IIC gas
group vapors present.