Connecting the Detector

27

2.7

Connecting the Detector

This section describes how to connect the electric cabling to the detector
(figure 7).

To connect the detector to the electrical cables

1

Disconnect the power.

2

Remove the back cover of the detector by removing four (4) socket
head-screws in the cover bolts. The terminal chamber is now revealed.

3

Remove the protective plug mounted on the Detector Conduit/Cable
entry; pull the wires through the Detector Inlet.

4

Use a ¾" – 14 NPT explosion-proof conduit connection or M25x1.5
flameproof gland to assemble the cable / conduit to the detector.

Figure 7: Detector with Cover Removed

5

Connect the wires to the required terminals on the Terminal Board
according to the wiring diagram (figure 7) and table 16.

6

Connect the grounding (earth) wire to the ground (earth) screw outside
the detector (Earth Terminal). The detector must be well grounded to
earth ground.

Earth

Terminal

Terminal

Chamber

Terminals

Internal Earth

Terminal

Detector Holding

Screw
Conduit / Cable
Inlet