5 output signals, Output signals, Table 5: available output types – Spectrex 40/40UFL Ultra Fast UV/IR User Manual
Page 25
TM 40/40UFL, Rev (2) August 2013
Performance Considerations
13
1.5.5 Output Signals
Outputs are available according to the default configuration or the wiring
options selected for the 40/40UFL detector. Determine the outputs for your
model according to Table 5.
The detector incorporates several types of output suitable to different
control systems:
0-20mA (stepped) with HART
Relays (Alarm, Fault, Auxiliary)
RS-485 Modbus
Analog Output – analog output proved ultra-fast detection to comply
with 20 msec detection.
Table 5: Available Output Types
Output Type
Version
Detector Status
Alarm relay
Options 1XXXX, 4XXXX,
5XXXX
The relay is N.O.
Options 2XXXX, 3XXXX
The relay is N.O. and N.C.
Auxiliary relay
Options 4XXXX and
5XXXX
The relay is N.O.
Fault relay
Options 1XXXX, 2XXXX,
4XXXX
The relay is N.C. energized
Options 3XXXX, 5XXXX
The relay is N.O. energized
0-20mA
Current Output
Option 1XXXX
SINK Option, (can be
changed to Source – see
Figure 10, Figure 11 and
Figure 12)
Options 2XXXX and
3XXXX
SOURCE Option with the
HART protocol
RS-485
All versions
Modbus protocol
Analog Output
All Versions
0 V during Normal
5 V during detection