SECTION 1

Product Description

The DACT-UD2 (Digital Alarm Communicator/Transmitter) transmits system status to
UL listed Central Station Receivers via the public switched telephone network. The
communicator mounts to the FACP main circuit board inside the panel cabinet and is
capable of reporting 636 points or 99 zones. The DACT-UD2 is supplied standard with
the MS-9600UDLS/E and is optional for the MS-9600LS/E.

1.1 Product Features

Dual supervised telephone lines

Mounts inside the control panel

Extensive transient protection

Communicates vital system status including:

Independent zone/point alarm
Independent zone/point trouble
Independent zone/point supervisory
AC power loss
Low/No battery
Battery charger trouble
Earth fault
System off normal
12 or 24 hour test signal with alternating phone lines
Abnormal test signal
Annunciation at control panel of DACT troubles including loss of phone lines,

communication failure with either Central Station, total communication failure

NAC faults
SLC faults
Annunciator/option faults

1.2 Compatible Panel

The DACT-UD2 has been designed to be compatible with the following control panel:

MS-9600LS

MS-9600UDLS

1.3 Specifications

DC Power - J1 Connector

Current draw in standby and alarm:

U Standby = 0.0193 amps max.
U Alarm = 0.0335 amps max. (communicating)