Programming for DACT-UD2
18
DACT-UD2 Communicator PN 53037:B 4/01/08
SECTION 3
Programming for DACT-UD2
3.1 Programming the MS-9600LS Fire Alarm Control Panel
Refer to the MS-9600LS Manual programming section for general programming
information. To program the MS-9600LS FACP for use with the DACT-UD2:
1. Press the Enter or Mode key to display the Read Status/Programming screen
2. Press 2 to access Programming
3. Enter the Master level password
4. Press the down arrow key twice to view the screen with the Option Modules
choice
5. Press 3 for Option Modules to access the Option Modules screen as shown to the
left
6. Program the FACP for use with the DACT-UD2 using the following procedure
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in ANSI/UL
864, Standard for Control Units and Accessories for Fire Alarm Systems, certain programming features or options must be lim-
ited to specific values or not used at all as indicated below:
Program feature
or option
Permitted in
ANSI/UL 864?
(Y/N)
Possible settings
Settings permitted
in ANSI/UL 864
Trouble Call Limit
N
Refer to "Trouble Call Limit (Dialer Runaway Prevention)"
on page 22.
Trouble Call Limit = 0 (factory default): unlimited
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Trouble Call Limit =
0 for unlimited
Central Station
trouble calls
Remote Download
Y
Refer to
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Remote Download
Proprietary Yes for
Proprietary
Installations Only