1 on-board dact – Fire-Lite DACT-UD2 Digital Alarm Communicator/Transmitter User Manual
Page 19

Programming for DACT-UD2
DACT-UD2 Communicator PN 53037:B 4/01/08
19
3.1.1 On-Board DACT
The DACT-UD2 (Digital Alarm Communicator/Transmitter) is an optional module
which installs directly on the FACP main circuit board for communication to a
central station. Pressing 2 while viewing the Option Module Screen will cause the
following screens to be displayed:
3.1.1.1 DACT-UD2 DACT Enable
To enable the on-board DACT-UD2 module, press 1 while viewing On Board
DACT Screen #1 until the display reads Enabled Yes. The display will toggle
between Enabled Yes and Enabled No with each press of the key.
3.1.1.2 Primary Phone
Press 2 while viewing On Board DACT Screen #1 to program the type of primary
phone line being connected to the DACT-UD2. The following screen will be
displayed:
To select the type, press 1 while viewing the Primary Phone Line screen. The
following screen will be displayed:
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break
ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ON BOARD DACT
3=PRINTER/PC
Option Module Screen
ON BOARD DACT
1=ENABLED YES
2=PRIMARY PHONE
3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
ON BOARD DACT
PRIMARY PHONE LINE
1=TYPE TOUCHTONE
Primary Phone Line Screen
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 60/40
Primary Phone Type Screen