Central Station Communications

DACT-UD2 Communicator PN 53037:B 4/01/08

31

4.1 Transmittal Priorities

The DACT-UD2 transmits highest priority events first. Events, in terms of priority, are
listed below in descending order:

1. Alarms (highest priority level)

Pull stations

Waterflow

Smoke detector

Other alarm types

2. Supervisory Zone

3. System Troubles

Zone disabled

Fire drill

AC fail (after delay)

Zonal faults

Earth fault

Low battery/no battery

Telephone line fault

Notification Appliance Circuits fault

Communication trouble

Annunciator trouble

System off normal

4. Restoral Reports

Zone alarm

Supervisory

Zone(s) enabled

Fire drill

AC

Zone fault

Earth

Battery

Telephone line

Notification Appliance Circuits

Communication

Annunciator trouble

System off normal

5. 24 Hour Test (lowest priority)