Fire-Lite DACT-UD2 Digital Alarm Communicator/Transmitter User Manual
Page 26

Programming for DACT-UD2
26
DACT-UD2 Communicator PN 53037:B 4/01/08
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following
screen to be displayed:
The Communication Format is determined by the type of receiver that the
DACT-UD2 is transmitting to. Consult your Central Station for proper selection or
consult our factory representatives. For any format chosen, the control panel
automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while
viewing the appropriate Comm Format screen. The following table describes each
format:
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following
screen to be displayed:
Pressing the down arrow key allows viewing of all Events associated with the
selected Communication Format. Pressing the number corresponding to the event
displayed in each screen will display its default event code which can be customized
by the programmer. For example, pressing 1 for Pull Station will display a screen
similar to the following which allows the Event Code to be changed from the
default value.
The tables on the following pages list all of the Events and their default Event
Codes for the various Communication Formats.
Table 3.1 Communication Formats
Screen Selection
Communication Format Description
ADEMCO CONTACT ID
Contact ID, DTMF, 1400/2300 ACK
SIA 8
Security Industry Association, 8 messages per call
SIA 20
Security Industry Association, 20 messages per call
CENTRAL STATION
1=COMM FORMAT
Primary/Secondary Screen #3
COMM FORMAT
1=ADEMCO CONTACT ID
2=SIA 8
3=SIA 20
Comm Format Screen
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Event Code Screen
PULL STATION 115
Event Code Screen