Normal operation – Fire-Lite CHG-120F Battery Charger User Manual
Page 26

Operating the Charger
Normal Operation
26
CHG-120F Instruction 03/21/01 PN 50888:B0
Table 7 shows the conditions that cause the charger LEDs to come on:
Normal Operation
The CHG-120F charges batteries at 4.5 A. When batteries are fully charged, the charger
maintains a float charge of 27.6 VDC at a trickle charge rate of less than 400 mA. While
charging the batteries, the HI and LO Charge LEDs switch on and off approximately every
20 seconds. Also, one of the 23 V, 25 V, 27 V, or Low Battery LEDs also comes on,
depending on the battery voltage.
LED
No
rm
al
Ope
rat
io
n
A
C
T
ro
ubl
e
Di
sc
on
n
e
cted
Ba
ttery
Gr
ou
nd F
a
ult
Sho
rt
C
ir
cui
t
F
a
ulty
Ba
tte
ry
(o
r less th
e
2
1
V)
T
ro
u
b
le
(w
ith
A
C
T
ro
ubl
e
De
lay u
sed
)
T
rou
bl
e (
M
ast
e
r T
rou
b
le
I
n
J
P
6 con
n
ected
)
AC On
Trouble
Ground Fault
HI Charge
✩
✩
✩
✩
✩
LO Charge
(Loss of AC)
✩
✩
✩
✩
27 V
✩
✩
✩
✩
✩
25 V
✩
✩
✩
✩
✩
23 V
✩
✩
✩
✩
✩
Low Battery
✩
✩
✩
✩
✩
Legend:
LED on.
✩
LED on or off, depending on battery voltage. Refer to “Normal Operation.”
Table 7 LED Status Indicators
- 2401B Circuit Board Standoff Placement (1 page)
- 411UDAC Fire Alarm Communicator (84 pages)
- 411UDAC Dig C Digital Communica unicatortor (1 page)
- 411UDAC Communicator Dress Panel (2 pages)
- 411UDAC Communicator Circuit Board & Transformer (2 pages)
- 411UDAC Fire Alarm Communicator Relay (1 page)
- ACC-25/50 Audio Command Center (1 page)
- ACC-25/50DA Distributed Audio Panel (84 pages)
- ACC-25/50ZS (1 page)
- ACM-16ATF Annunciator Modules (68 pages)
- ACM-8RF Control Relay Module (48 pages)
- APS-6RF Auxiliary Power Supply (28 pages)
- B524BI Plug-in Isolator (4 pages)
- B524RB(A) Plug-in Relay Detector Bases (4 pages)
- B310LP Plug-in Base for Addressable Detector (2 pages)
- B350LP Plug-In Base for Addressable Detector (4 pages)
- BB-55 Battery Box (1 page)
- BG-12 Series Manual Pull Stations (4 pages)
- BG-12LA Manual Pull Station (2 pages)
- BG-12LAO Manual Pull Station (2 pages)
- BG-12LO Manual Pull Station (2 pages)
- BG-12LPS Pre-Signal Manual Pull Station (2 pages)
- BG-12LR Agent Release Pull Station (2 pages)
- BG-12LX Addressable Pull Station (2 pages)
- BG-12SL Single Action Pull Station (2 pages)
- Central Station Receiver (1 page)
- CHG-120 Series Addendum - For Connection Of 100 Amp Hour Batteries (2 pages)
- CHG-75 Battery Charger (32 pages)
- CHS-6 Chassis (1 page)
- CHS-6 Chassis for BB-6 Cabinet (1 page)
- CMP-2401B Fire Alarm Control Panel (36 pages)
- CP355 Plug-in Addressable Ionization Sensor (2 pages)
- CRF-300 Relay Control Module (2 pages)
- DACT-UD2 Digital Alarm Communicator/Transmitter (52 pages)
- DP-4XF Dress Panel Kit PID (2 pages)
- ECC-50/100 Emergency Command Center (108 pages)
- ECC-50WBU Backup Amplifier (1 page)
- ECC-50DA/E Distributed Audio Amplifiers (26 pages)
- ECC-FFT (1 page)
- FCPS Series Field Charger/Power Supply (48 pages)
- FCPS Series Field Software Change Procedure (2 pages)
- FHSC-RF FIREFIGHTERS HANDSET STORAGE BOX (1 page)
- ECC-FFT Firefighters Telephone (32 pages)
- H350 Addressable Thermal Sensor (2 pages)