beautypg.com

Operating the charger, Overview, Starting the charger – Fire-Lite CHG-120F Battery Charger User Manual

Page 25: Understanding the led status indicators

background image

CHG-120F Instruction 03/21/01 PN 50888:B0

25

3. Operating the Charger

Overview

This section contains information on starting the charger, interpreting the LED Status
Indicators on the charger, and normal operation of the charger.

Starting the Charger

Warning: Before starting the charger, do the following:

†

Follow the installation instructions in Section 2, “Installing the Charger.”

†

Verify proper polarity on all connections between the charger and the batteries, load,
and optional meters.

†

Make sure there are no short circuits between leads and between battery terminals

†

Make sure the Battery Interconnect Cable(s) is not connected

To start the charger, follow these steps:

1.

Connect AC power to the charger. The AC On LED and Trouble LED turn on

2.

Connect the batteries to the charger

3.

Connect the Battery Interconnect Cable. The Trouble LED turns off

4.

Connect the charger to the load (such as a power supply, an amplifier, etc.)

Understanding the LED Status Indicators

The charger provides nine LED Status Indicators, which are identified in Figure 18. Also
refer to Table 7 for conditions, such as troubles, that cause LEDs to light.

Figure 18 LED Status Indicators

AC On - Primary AC on

Trouble - Charger in trouble condition (see Table 7)

Ground Fault - Earth fault condition detected

HI Charge - Charging current greater than 400 mA

LO Charge - Charging current less than 400 mA (loss of AC)

27V - Battery voltage greater than 27 VDC

25V - Battery voltage between 25-27 VDC

23V - Battery voltage between 23-25 VDC

Low Battery - Battery voltage less than 23 VDC

Green LED