Connecting Batteries to the Charger

Installing the Charger

CHG-120F Instruction 03/21/01 PN 50888:B0

13

Connecting Four Batteries - Figure 6 illustrates how to connect four 55 AH batteries to
the charger:

Figure 6 Connecting Four Batteries to a Charger

Table 4 contains instructions for connecting four batteries to the charger:

Warning: Do not
connect the Battery
Interconnect Cable
at this time.

Refer to “Starting the
Charger” on page 25.

!

TB2

Step Action

1

Remove all power sources to the charger.

2

Tie the batteries in pairs by connecting the battery negative terminals and the
battery positive terminals as shown in Figure 6.

3

Connect the battery negative cable to the TB2 terminal (on the charger) labeled
“Battery –” as shown in Figure 6.

4

Connect the battery positive cable to the TB2 terminal (on the charger) labeled
“Battery +” as shown in Figure 6.

5

Proceed to the section “Connecting the Charger.” Do not connect the Battery
Interconnect Cable at this time
—refer to “Starting the Charger” on page 25.

Table 4 Connecting 55 AH Batteries