Ordering/Electrical Specifications
PART NUMBER
POWER INPUT (L1, L2)
INPUT FUSE REQUIRED
INT-05-024
1
24VDC +/-15%
Fast acting 1/4A (250V, 5 x 20mm, F)
INT-05-120
2
120VAC +10% -20%, 5VA, 50/60Hz
Fast acting 80mA (250V, 5 x 20mm, F)
1
Max of 80 expansion relays in series with INT-03 or INT-04.
2
Max of 1 expansion relay in series with INT-03 or INT-04.
RESET
A
SAFE
AUX.
B
C
D
E
F
G
OUTPUTS
230 VAC
60 VDC
120 VAC
30 VDC
LOADS
L1
L2
A
SAFE
FBK
B
C
D
X1
Expansion Relay
INT-05
X2 Y1
Y2
E
F
G
H
INT05WIR
OUTPUTS
24 VDC for -024
120 VAC for -120
230 VAC
60 VDC
LOADS
FUSE
–
+
L1
L2
1
2
X1 X2
Y1
Y2
N.O.
N.C.
Safety Monitor Relay
INT-03
General Specifications
UL/CSA/TUV
CSA submitted
Environmental Rating
Pollution Degree II
Temperature Range
32
°
F to 149
°
F (-0
°
C to 65
°
C)
Relative Humidity
30 to 95% non-condensing
Control Inputs (X1, X2 & Y1, Y2 terminals)
Open-circuit voltage
24VDC
Closed-circuit current
24mA
Max. contact resistance
30 Ohms
Simultaneity
500 ms typical
Safe Outputs (A,B/C,D/E,F terminals)
Voltage
230 VAC/60VDC
Current
4A (resistive) each output
Response time
ON: <40ms, OFF:<30ms
Fuse
4A, 250V, 5 x 20 mm
AUX. Signaling Outputs (F1,F2 terminals)
Voltage
120 VAC/30VDC
Current
1A (resistive)
Note: Transient protection is required across the load when switching an
inductive load.
Typical Wiring Diagram
European Directives
Machinery Directive (98/37/EEC)
Low Voltage Directive (73/23/EEC), LVD
Specific European Standards
EN60204-1 Safety of electrical equipment of industrial
machines: 1993
EN954-1 Risk Assessment Category 4
depending on wiring method, See diagrams: 1997
EN50081-2 Electromagnetic Emissions: 1995
EN50082-2 Electromagnetic Immunity: 1995
IEC 664-1 Insulation requirements: 1992
IEC 68, part 2-1, 2-2, 2-3, 2-6, 2-14, 2-27, 2-30.
EN1760-1:1998
Declaration of Conformity
available upon request.
File E 122942