Edwards Signaling HSL Series User Manual
Page 4

Electrical
Manufacturers
Replacement
Lamp Life (hours)
Catalog No.
Ratings
Lamp Ratings
Lamp
Calculated
#
Projected
##
Base Units
102TBS-G1
24V DC, 1.75A
+
N/A
N/A
N/A
N/A
102TBS-N5
120V AC, 0.60A
+
Optional Pipe Mount Flange
102PMF
N/A
N/A
N/A
N/A
N/A
Optional Extension Pipes
102MP-4
N/A
N/A
N/A
N/A
N/A
102MP-10
N/A
N/A
N/A
N/A
N/A
102MP-15
N/A
N/A
N/A
N/A
N/A
Horn Assembly
102SIGMT-G1
24V DC, 0.05A
N/A
N/A
N/A
N/A
102SIGMT-N5
120V AC, 0.07A
Lens Modules
102LM-*
N/A
N/A
N/A
N/A
N/A
Light Sources
102LS-SIN-G1
24V DC, 0.32A
10 Watts
Ind. Trade 303
10,000
--
102LS-SIN-N5
120V AC, 0.08A
10 Watts
50LMP-10W
2,500
--
102LS-SLEDA-G1**
24V DC, 0.062A
--
N/A
100,000
--
102LS-SLEDB-G1**
102LS-SLEDG-G1**
102LS-SLEDR-G1**
102LS-SLEDW-G1**
102LS-SLEDA-N5**
120V AC, 0.022A
--
N/A
100,000
--
102LS-SLEDB-N5**
102LS-SLEDG-N5**
102LS-SLEDR-N5**
102LS-SLEDW-N5**
+
Currents shown are for a stackable indicator with 5 light modules.
*Signifies lens module color (A - amber/orange, B - blue, C - clear, G - green, R - red, Y - yellow)
**Signifies lens and LED module color (A - amber/orange, B - blue, G - green, R - red) NOTE: LED light sources must be used with the
corresponding color lens module (e.g., a blue LED light source, 102LS-SLEDB-G1, must be used with a blue lens, 102LM-B). For yellow
modules, use the 102LS-SLEDW light source.
#
At nominal operating voltage.
##
Projected lamp life based on manufacturer's calculated lamp life @ 65 fpm and 50% duty cycle.
Table 1. Specifications
Table 2. PLC Compatibility
Unit input
Maximum leakage
Continuous on
Peak current
Cat. No.
voltage*
current (mA)
current (mA)
inrush/duration (A/ms**)
102SIGMT-G1
24V DC
5
50
0.24/0.2
102SIGMT-N5
120V AC
5
70
0.35/0.5
102LS-SIN-G1
24V DC
25
32
0.36/1
102LS-SIN-N5
120V AC
25
80
0.15/8
102LS-SLED( )-G1
24V DC
5
65
0.07/1
102LS-SLED( )-N5
120V AC
5
25
0.09/8
*All AC volts at 60 Hz
**Amps/milliseconds
P/N 3100661 ISSUE 1