Edwards Signaling 105XBRM User Manual
Warning
Installation Instructions for Cat. 105XBRM Series
Adverse Location Visual Signals
Description
The 105XBRM Series visual signals are heavy duty, reliable,
UL, cUL (General Utility) (misc. device/control unit accessory)
beacons which, when assembled in accordance with instal-
lation instructions, constitute a UL listed Type 4X enclosure
and are UL Listed for Marine Use. They are designed for use
in industrial applications or in applications where a Type 4X
enclosure is required. The 105XBRM LED Series are factory
shipped in a steady-on mode. The device can be easily set
to 65 fpm flashing mode. When assembled in accordance
3. Install the mounting attachment as follows:
a. Cat. No. 105BX: Secure the outlet box attachment to
the mounting surface using two screws (not supplied)
suitable for the surface. Attach the adhesive backed
gasket to the top of the 105BX mounting box, being
careful to line up the holes in the gasket with the
mounting holes in the outlet box.
b. Cat. No. 105BM: Using the four supplied screws,
secure the mounting bracket to Cat. No. 105BX
outlet box attachment as shown in Figure 1. Attach
the adhesive backed gasket to the top of the 105BM
mounting bracket, being careful to line up the holes
in the gasket with the mounting holes in the outlet
box.
c. Cat. No. 105PM: Install 3/4" (19 mm) conduit.
Screw the pipe mount attachment onto the 3/4" (19
mm) conduit. Attach the adhesive backed gasket
to the top of the 105PM pipe mount attachment,
being careful to line up the holes in the gasket with
the mounting holes in the outlet box.
4. Unscrew the lens from the base.
5. The 105XBRM Series Visual Indicator is supplied with a
default setting of steady-on. If 65 fpm pattern is desired,
set dipswitch as shown in Figures 2 & 4.
6. Secure the base to the appropriate mounting attachment
using four screws (supplied). Replace the clear gasket
on the base with the flared, open end facing down.
7. Attach the unit's 18" wire leads to the field wiring as
shown in Figure 3.
Installation must be in accordance with local codes. The lens
should be positioned up for outdoor applications.
1. Select a mounting configuration (Figure 5).
NOTE: When mounting using the Cat. No. 105BM
mounting bracket, the Cat. No. 105BX outlet box
attachment must also be used as shown in Figure
1.
2. Pull field wiring into the mounting attachment.
Table 1. Hazardous Location Ratings
Cat. No.
Class
Division
Group
Operating Temperature
105XBRM( )24D
I
2
A, B, C, D
T4A (120C, 248F)
105XBRM( )120A
I I
2
F, G
T4A (120C, 248F)
I I I
T4A (120C, 248F)
Installation
with these instructions, the 105XBRM Series visual signals
are UL Listed for use in Hazardous Locations with Operating
Temperatures listed in Table 1.
For specification details, see Table 2.
Mechanical Specifications
Outdoor Locations
Temperature Ratings ........... -31F to +150F (-35C to +66C)
To prevent electrical shock, do not connect
power until instructed to do so.
WARNING
The 105BX junction box, 105BM mounting
bracket and 105PM pipe mount attachments
are non-conductive plastic fixtures and
do not provide earth-ground continuity
when attached to metallic wiring systems.
Therefore, they are intended for use with the
105XBRM Series visual signals only when
earth-grounding is not required.
The 105BX junction box, 105BM mounting
bracket and 105PM pipe mount attachments
can be used with metallic wiring systems
only when installed at the end of a run.
WARNING
P/N 3101571 ISSUE 3
© 2010
http://www.edwardssignaling.com Phone: (800) 336-4206 Fax: (800) 454-2363