Installation Instructions for Cat. 105XBRM Series

Adverse Location Visual Signals

Description

The 105XBRM Series visual signals are heavy duty, reliable,

UL, cUL (General Utility) (misc. device/control unit accessory)

beacons which, when assembled in accordance with instal-

lation instructions, constitute a UL listed Type 4X enclosure

and are UL Listed for Marine Use. They are designed for use

in industrial applications or in applications where a Type 4X

enclosure is required. The 105XBRM LED Series are factory

shipped in a steady-on mode. The device can be easily set

to 65 fpm flashing mode. When assembled in accordance

3. Install the mounting attachment as follows:

a. Cat. No. 105BX: Secure the outlet box attachment to

the mounting surface using two screws (not supplied)

suitable for the surface. Attach the adhesive backed

gasket to the top of the 105BX mounting box, being

careful to line up the holes in the gasket with the

mounting holes in the outlet box.

b. Cat. No. 105BM: Using the four supplied screws,

secure the mounting bracket to Cat. No. 105BX

outlet box attachment as shown in Figure 1. Attach

the adhesive backed gasket to the top of the 105BM

mounting bracket, being careful to line up the holes

in the gasket with the mounting holes in the outlet

box.

c. Cat. No. 105PM: Install 3/4" (19 mm) conduit.

Screw the pipe mount attachment onto the 3/4" (19

mm) conduit. Attach the adhesive backed gasket

to the top of the 105PM pipe mount attachment,

being careful to line up the holes in the gasket with

the mounting holes in the outlet box.

4. Unscrew the lens from the base.
5. The 105XBRM Series Visual Indicator is supplied with a

default setting of steady-on. If 65 fpm pattern is desired,

set dipswitch as shown in Figures 2 & 4.

6. Secure the base to the appropriate mounting attachment

using four screws (supplied). Replace the clear gasket

on the base with the flared, open end facing down.

7. Attach the unit's 18" wire leads to the field wiring as

shown in Figure 3.

Installation must be in accordance with local codes. The lens

should be positioned up for outdoor applications.
1. Select a mounting configuration (Figure 5).
NOTE: When mounting using the Cat. No. 105BM

mounting bracket, the Cat. No. 105BX outlet box

attachment must also be used as shown in Figure

1.

2. Pull field wiring into the mounting attachment.

Table 1. Hazardous Location Ratings

Cat. No.

Class

Division

Group

Operating Temperature

105XBRM( )24D

I

2

A, B, C, D

T4A (120C, 248F)

105XBRM( )120A

I I

2

F, G

T4A (120C, 248F)

I I I

T4A (120C, 248F)

Installation

with these instructions, the 105XBRM Series visual signals

are UL Listed for use in Hazardous Locations with Operating

Temperatures listed in Table 1.
For specification details, see Table 2.

Mechanical Specifications

Outdoor Locations

Temperature Ratings ........... -31F to +150F (-35C to +66C)

To prevent electrical shock, do not connect

power until instructed to do so.

WARNING

The 105BX junction box, 105BM mounting

bracket and 105PM pipe mount attachments

are non-conductive plastic fixtures and

do not provide earth-ground continuity

when attached to metallic wiring systems.

Therefore, they are intended for use with the

105XBRM Series visual signals only when

earth-grounding is not required.
The 105BX junction box, 105BM mounting

bracket and 105PM pipe mount attachments

can be used with metallic wiring systems

only when installed at the end of a run.