Specifications, Contact information – Edwards Signaling 5530MD-24AW User Manual
Page 6
6 / 24
P/N 3100007 • REV 07 • ISS 02JUL12
Tone
SW4-6 SW4-5 SW4-4 SW4-3 SW4-2 SW4-1 Description
HEX
Yellow Rose of Texas
19.34 seconds of melody followed by 1 second
delay and repeat
3B
[1] 3 Pulse Tones are for evacuation use only. 3 Pulse Horn, 3 Pulse Air Horn, and 3 Pulse Dual Tone are used for ULC Fire installations.
Closed/On switch=
Open/Off switch=
Caution:
The use of evacuation signals on this product, that is not specifically listed for fire alarm use, is subject to the approval of
the authority having jurisdiction.
Specifications
Mechanical specifications
Weight
9 lb. (4.1 kg)
Temperature
Hazardous Locations, UL
Standard UL1604 Ambient
Temp.
Non-Hazardous Locations
Variable Ambient Temp.
-31°F to +104°F (-35°C to +40°C)
-40°F to +151°F (-40°C to +66°C)
Note: Hazardous locations and variable ambient conditions apply only
where UL Listings are accepted.
Electrical specifications
Catalog number
Voltage
Current (A) tone on
5530MD-24AW 20
VDC
0.63
24
VDC
0.74
28
VDC
1.0
31
VDC
0.85
20 VFWR 120 Hz
0.69
24 VFWR 120 Hz
0.79
Directional characteristics at power input voltage
Specification
Output sound pressure level at
3 meters
Rated on axis: 0°
85 dBA
Horizontal axis:
65 deg and 115 deg
60 deg and 125 deg
-3 dBA
-6 dBA
Vertical axis:
70 deg and 110 deg
60 deg and 125 deg
-3 dBA
-6 dBA
Wire gauge
22 to 12 AWG
Contact information
For contact information, see www.edwardssignaling.com.