Edwards Signaling 2453BSA User Manual
Page 2
P-047550-1720 ISSUE 3 © 1997
Indoor Bell/Strobe Adapter Plate,
403-3A-R
30 cd, Red
XLS403-3A-R
2453BSA-30-R
BS-3AR
Indoor Bell/Strobe Adapter Plate,
403-5A-R
15 cd, Red
XLS403-5A-R
BS-5AR
Indoor Bell/Strobe Adapter Plate,
403-7A-R
15/75 cd, Red
XLS403-7A-R
2453BSA-15/75-R
BS-7AR
Indoor Bell/Strobe Adapter Plate,
403-8A-R
110 cd, Red
XLS403-8A-R
2453BSA-110-R
BS-8AR
Operating Voltage
20-24V DC
Operating Current
See Figure 3
Flash Rate (per second)
1 fps (synchronized)
3A
5A*
7A
8A
Light Output (cd)
UL 1971
30 cd wall
15 cd
15 cd wall
110 cd wall
UL 1638
30 cd
not rated
75 cd
120 cd
ULC S526
30 cd
15 cd
75 cd
120 cd
Operating Environment
Indoor 93% relative humidity @ 86F (30C), 32F to 120F (0C to
49C) variable ambient temperature
*The 5A model is for wall mount use only.
NOTE: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause
harmful intereference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user will be required to correct
the interference at his own expense.
CAUTION: Changes or modifications to this equipment not expressly approved by the party
responsible for compliance could void the user's authority to operate the equipment.
Same Signal Circuit
The bell and strobe can be connected to the same
signal circuit (as shown) if the circuit is configured for
continuous signal operation.
Caution: Electrical supervision requires wire run to be
broken at each device. Do not loop signal circuit field
wires around the Bell/Strobe unit leads.
Separate Signal Circuits
The bell and strobe can be connected to different
signal circuits (as shown). The strobe is designed to
be used on circuits that output a constant voltage. Do
not connect the strobe to a coded or pulsating voltage.
Caution: Electrical supervision requires wire run to be
broken at each device. Do not loop signal circuit field
wires around the Bell/Strobe unit leads.
Figure 2. Connecting Strobe Unit
Table 1. Specifications
Table 2. Bell/Strobe Adapter Plates