Table 1. 107DV2 Series AdaptaBeacon Strobes

Mounting

Conduit

Flash

Strobe Tube

Catalog Number

Method

Voltage

Current

Size

Rate

Replacement

107DV2PST*-N5

Pendant

120V 60 Hz

0.1A

3/4" NPT

Approx.

92-ST

107DV2BST*-N5

Bracket

65 fpm

107DV2CST*-N5

Ceiling

107DV2PST*-R5

Pendant

240V 60 Hz

0.05A

3/4" NPT

Approx.

92-ST

107DV2BST*-R5

Bracket

65 fpm

107DV2BST*-R5

Ceiling

107DV2PST*-EK

Pendant

12-48V DC

1.2-0.38A

3/4" NPT

Approx.

92-ST

107DV2BST*-EK

Bracket

65 fpm

107DV2CST*-EK

Ceiling

107DV2PST*-S1

Pendant

250V DC

0.1A

3/4" NPT

Approx.

92-ST

107DV2BST*-S1

Bracket

65 fpm

107DV2BST*-S1

Ceiling

*Letter in this position denotes color of the globe: A - amber, B - blue, C - clear, G - green, R - red or
M - magenta

Figure 4. Disassembly of the 107DV2 Series Adaptabeacons

Table 2. Supply Wire Temperature Markings

Ambient

Supply Wire

Temperature

Temperature Marking

40°C

60°C

55°C

75°C

65°C

90°C

OUTER GLOBE

(2) SCREWS HOLDING CIRCUIT

ASSEMBLY TO THE FIXTURE

CEILING MOUNT

OUTLET BOX

GASKET