Installation Instructions for 107DV2 Series AdaptaBeacon

®

Strobe Light for Use in Hazardous Locations

Description

Description

Description

Description

Description

The 107DV2 Series AdaptaBeacon strobe signaling appli-

ances are intended for general utility signaling use. They

are available in pendant, bracket or ceiling mount con-

figurations and in 12-48V DC, 250V DC, 120V 60 Hz and

240V 60 Hz. They are UL and cUL Listed for use in Class I,

Division 2, Group A, B, C and D hazardous locations; pen-

dant-mount versions with clear globes are also listed for

Class II, Division 1, Group E, F and G, Class II, Division 2,

Group F and G, and Class III Division 1 and 2 hazardous

locations. Operating Temperature Codes are per the fol-

lowing chart.

supplied) for the mounting surface. Pull the field

wiring through the outlet box.
Ground the unit in accordance with National Electrical

Code (NFPA 70) and local requirements.
Connect red positive (+) wire lead to incoming positive

(+) and connect black negative (-) wire lead to

incoming negative using wire nuts (not supplied).
Mount the wall bracket back onto the outlet box.

3. Ceiling Mount Installation (Figures 3 and 4):

Unscrew and remove the clear outer globe. Remove

the two screws holding the circuit assembly to the

bottom of the fixture. To separate the ceiling junction

box from the fixture housing, remove the remaining

two screws at the bottom of the fixture.
Mount the ceiling junction box using appropriate

hardware. Pull power source wiring through the

ceiling junction box.
Ground the unit in accordance with National Electrical

Code (NFPA 70) and local requirements.
Connect the positive (+) power source wire to the

positive (+) terminal and the negative (-) power source

wire to the negative (-) terminal.
Secure the fixture housing on the junction box by

replacing the two screws removed above. Reinstall

the circuit assembly to the bottom of the fixture using

the two screws removed above.
Screw the clear outer globe back on the fixture

housing.

4. Where applicable, install the optional guard assembly

over the clear outer globe and secure using three screws

(provided).

Figure 1. Detail of Pendant Mounting

WARNING

To reduce the risks of ignition of hazardous atmo-
spheres and shock, do not apply power to the unit
until installation has been completed and unit is
tightly assembled and secured.

Install this unit in accordance with the applicable require-

ments in the latest edition of the National Electrical Code

or Canadian Electrical Code, using supply wire rated per

Table 2.
1. Pendant Mount Models (Figure 1): Install explosion-

proof hanger box (not supplied). Pull the unit's wire

leads through the 3/4" (19 mm) NPT threaded conduit

(not supplied). Secure the 3/4" (19 mm) threaded

conduit to the mounting hood.
Ground the unit in accordance with National Electrical

Code (NFPA 70) and local requirements.
Connect red positive (+) wire lead to incoming positive

(+) and connect black negative (-) wire lead to

incoming negative using wire nuts (not supplied).
Secure the 3/4" (19 mm) threaded conduit to the outlet

box.

2. Bracket Mount Models (Figure 2): Remove the

outlet box from the end of the mounting bracket.

Install the outlet box using appropriate hardware (not

They are UL and cUL listed as Type 3R and 4. AC rated

strobes are also UL and cUL listed for Marine.
The strobe flashes a 360-degree beam of light approxi-

mately 65 times per minute.

Installation

Installation

Installation

Installation

Installation

WARNING

To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.

Operating Temperature Codes

NOTE: Class II and Class III only apply to

Pendant Mount with clear globes

Class II, Div. 2,

Groups F, G;

Class III, Div. 2
Class II, Div. 1,

Ambient

Class I, Div. 2

Groups E, F, G;

Temp.

Groups A, B, C, D

Class III, Div. 1

40

°

C

300

°

C (T2)

120

°

C (T4A)

55

°

C

450

°

C (T1)

135

°

C (T4)

65

°

C

450

°

C (T1)

160

°

C (T3C)

5. Apply power to the unit and ensure proper function.

9 7/8"

(251mm)

10 1/4"

(260mm)

7"

(172mm)