Edwards Signaling 105 Series User Manual
Warning, Description, Installation
Installation Instructions for Cat. 105 Series
Adverse Location Visual Signals
Description
The 105 Series visual signals are heavy duty, reliable, UL,
cUL (General Utility) and CSFM listed (misc. device/control
unit accessory) beacons which, when assembled in accor-
dance with installation instructions, constitute a UL listed
Type 4X enclosure and are UL Listed for Marine Use. They
are designed for use in industrial applications or in appli-
3. Install the mounting attachment as follows:
a. Cat. No. 105BX: Screw the outlet box attachment
to the mounting surface using two screws (not
supplied). suitable for the surface. Attach the
adhesive backed gasket to the top of the 105BX
mounting box, being careful to line up the holes
in the gasket with the mounting holes in the outlet
box.
b. Cat. No. 105BM: Using the four supplied screws,
secure the mounting bracket to Cat. No. 105BX
outlet box attachment as shown in Figure 1. Attach
the adhesive backed gasket to the top of the 105BM
mounting bracket, being careful to line up the
holes in the gasket with the mounting holes in
the outlet box.
c. Cat. No. 105PM: Install 3/4" (19 mm) conduit.
Screw the pipe mount attachment onto the 3/4"
(19 mm) conduit. Attach the adhesive backed
gasket to the top of the 105PM pipe mount
attachment, being careful to line up the holes in
WARNING
To prevent electrical shock, do not connect power
until instructed to do so.
Installation must be in accordance with local codes. The
lens should be positioned up for outdoor applications.
1. Select a mounting configuration (Figure 6).
NOTE: When mounting using the Cat. No. 105BM
mounting bracket, the Cat. No. 105BX outlet
box attachment must also be used as shown in
Figure 1.
2. Pull field wiring into the mounting attachment.
WARNING
The 105BX junction box, 105BM mounting bracket
and 105PM pipe mount attachments can be used with
metallic wiring systems only when installed at the
end of a run.
Table 1. Hazardous Location Ratings
Cat. No.
Class
Division
Group
Operating Temperature
105FINH*-G1
I
2
A, B, C, D
T2D (215C, 419F)
105SINH*-G1
I I
2
F, G
T4A (120C, 248F)
105FINH*-G5
I I I
T4A (120C, 248F)
105SINH*-G5
105FINH*-N5
I
2
A, B, C, D
T2 (300C, 572F)
105SINH*-N5
I I
2
F, G
T4 (135C, 275F)
I I I
T4 (135C, 275F)
105HIST*-N5
I
2
A, B, C, D
T2 (300C, 572F)
105HIST*-R5
I I
2
F, G
T3B (165C, 329F)
I I I
T3B (165C, 329F)
105HIST*-EK
I
2
A, B, C, D
T2A (280C, 536F)
I I
2
F, G
T3B (165C, 329F)
I I I
T3B (165C, 329F)
105ST*-G1
I
2
A, B, C, D
T3 (200C, 392F)
105ST*-N5
I I
2
F, G
T4A (120C, 248F)
105ST*-R5
I I I
T4A (120C, 248F)
105FLED*-N5
I
2
A, B, C, D
T5 (100C, 212F)
105SLED*-N5
I I
2
F, G
T5 (100C, 212F)
105FLED*-G1
I I I
T5 (100C, 212F)
105SLED*-G1
Installation
cations where a Type 4X enclosure is required. The units
are available in steady-on halogen or LED, flashing halo-
gen or LED, 3 Joule strobe or 8 Joule high intensity strobe.
When assembled in accordance with these instructions,
the 105 Series visual signals are UL Listed for use in Haz-
ardous Locations with Operating Temperatures listed in
Table 1.
For specification details, see Table 2.
P/N 3100290 ISSUE 3 © 2002
CHESHIRE, CT 203-699-3300 FAX 203-699-3365 (CUST. SERV.) 203-699-3078 (TECH SERV.)
WARNING
The 105BX junction box, 105BM mounting bracket
and 105PM pipe mount attachments are non-conduc-
tive plastic fixtures and do not provide earth-ground
continuity when attached to metallic wiring systems.
Therefore, they are intended for use with the 105
series visual signals only when earth-grounding is
not required.