beautypg.com

Caution – Edwards Signaling 101 Series User Manual

Page 4

background image

P-047550-1297 ISSUE 6

Steady-On Incandescent Light Unit*

120V AC

12V DC

24V DC

Lens Color

101SINHR-N5

101SINR-E1

101SINHR-G1

Red

101SINHA-N5

101SINA-E1

101SINHA-G1

Amber

101SINHB-N5

101SINB-E1

101SINHB-G1

Blue

101SINHG-N5

101SING-E1

101SINHG-G1

Green

101SINHM-N5

101SINM-E1

101SINHM-G1

Magenta

101SINHC-N5

101SINC-E1

101SINHC-G1

Clear

Steady-On LED Light Unit

120V AC

24V DC

Lens Color

101SLEDR-N5

101SLEDR-G1

Red

101SLEDA-N5

101SLEDA-G1

Amber

101SLEDB-N5

101SLEDB-G1

Blue

101SLEDG-N5

101SLEDG-G1

Green

Flashing Incandescent Light Unit*

120V AC

12V DC

24V DC

Lens Color

101FINHR-N5

101FINR-E1

101FINHR-G1

Red

101FINHA-N5

101FINA-E1

101FINHA-G1

Amber

101FINHB-N5

101FINB-E1

101FINHB-G1

Blue

101FINHG-N5

101FING-E1

101FINHG-G1

Green

101FINHM-N5

101FINM-E1

101FINHM-G1

Magenta

101FINHC-N5

101FINC-E1

101FINHC-G1

Clear

Flashing LED Light Unit

120V AC

24V DC

Lens Color

101FLEDR-N5

101FLEDR-G1

Red

101FLEDA-N5

101FLEDA-G1

Amber

101FLEDB-N5

101FLEDB-G1

Blue

101FLEDG-N5

101FLEDG-G1

Green

Flashing Strobe Light Unit

120V AC

12V DC

24V DC

Lens Color

101STR-N5

101STR-E1

101STR-G1

Red

101STA-N5

101STA-E1

101STA-G1

Amber

101STB-N5

101STB-E1

101STB-G1

Blue

101STG-N5

101STG-E1

101STG-G1

Green

101STM-N5

101STM-E1

101STM-G1

Magenta

101STC-N5

101STC-E1

101STC-G1

Clear

*H in catalog number (e.g., 101SINHR-N5) signifies halogen module.

3.

Loosen the slotted panhead through-bolt (on top module).
Do not remove the through-bolt from the module; turn the
bolt approximately 30 turns.

4.

Carefully remove the module and gasket.

5.

Continue to disassemble until the component to be replaced
is located and replace as follows.

Stackable Light Units Available

6.

Replace the incandescent or halogen lamp.

a.

Reach inside module, carefully grasp the lamp and press
down while turning counterclockwise to release.

b.

Place new lamp in socket and press down while turning
clockwise.

7.

Replace the strobe tube.

CAUTION

To prevent damage to the lamp,

do not touch glass

with bare fingers. Grasp glass with a soft, clean
cloth or with packaging supplied with the replace-
ment lamp.

a.

Reach inside module, grasp the base of the strobe tube
and remove.

b.

Holding the new strobe tube only by its base (if possible),
insert tube in socket.

8.

Replace mini pulsating horn.

a.

Remove the screw in the clamp ring, remove ring and
set aside.

b.

Remove three phillips head screws from top of base skirt
and remove the base skirt and the base/horn assembly
from the top portion of the base (Figure 2).

c.

Remove the phillips head screw securing the horn to the
mounting bracket (Figure 2).

d.

On DC models, disconnect wire leads from the terminal
blocks. On AC models, disconnect wires by cutting off
the wire crimp connectors.

e.

Secure the new horn on the mounting bracket with the
screw removed in step 8.c.

CAUTION

To prevent damage to the strobe tube,

do not touch

glass with bare fingers. Grasp the base of the
replacement strobe tube.