Maintenance

Caution: To maintain the required agency listings, do not

change factory-applied finishes.

This unit is not serviceable or repairable. Should the unit fail to

operate, contact the supplier for a replacement.
Perform a visual inspection and an operational test twice a

year or as directed by the local authority having jurisdiction.

Specifications


Operating voltage

24 VDC or 24 VFWR [1]

Current

Alarm

Operating

166 mA at 16 VDC, 215 mA at 16 VFWR

See Table 4

Sound level output

See Table 2 and Table 3

Audible directional

characteristics

See Table 5 and Table 6

Wire size

12 to 18 AWG (1.0 to 4.0 mm²)

Compatible electrical

boxes

Standard 4 in. square box 1-1/2 in. (38 mm),

2-1/8 in. (54 mm) deep box, or G4B/G4RB

surface mount box

Operating environment

Temperature

Relative humidity

32 to 120°F (0 to 49°C)

0 to 93% noncondensing

[1] This device was tested to the Regulated 24 DC/FWR operating

voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these

values for system operation.

Table 2: UL sound level output (dBA) [1]
Signal and voltage

Low

High

Temporal

16 VDC

72.4

76.0

24 VDC

72.3

75.7

33 VDC

73.3

75.4

Continuous

16 VDC

75.7

79.8

24 VDC

76.1

78.6

33 VDC

75.4

78.8

[1] UL 464: Sound level output at 10 ft. (3.05 m) measured in a

reverberant room

Table 3: Nominal sound level output (dBA, temporal tone) [1]
Voltage

Low

High

16 VDC

84.0

85.5

24 VDC

83.9

85.4

33 VDC

83.7

85.5

16 VFWR

83.7

86.1

24 VFWR

83.9

85.9

33 VFWR

84.0

85.9

[1] Measured in an anechoic chamber at 10 ft. (3.05 m)

Table 4: Nominal operating current in RMS (mA)
Signal and voltage

Low

High

Temporal

16 VDC

86

166

24 VDC

43

112

33 VDC

36

87

16 VFWR

97

215

24 VFWR

78

159

33 VFWR

76

140

Continuous

16 VDC

36

160

24 VDC

45

109

33 VDC

36

86

16 VFWR

92

212

24 VFWR

80

168

33 VFWR

77

141

VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified

Table 5: Audible directional characteristics (horizontal pattern)
Angle (°) [1]

Output (dB) [2]

0

85

+90

82

-90

82

[1] Angles are measured from a perpendicular axis; positive angles to

the right.
[2] Peak output at 16 VDC, set for steady tone.

Table 6: Audible directional characteristics (vertical pattern)
Angle (°) [1]

Output (dB) [2]

0

85

+90

82

−90

82

[1] Angles are measured from a perpendicular axis; positive angles are

up.
[2] Peak output at 16 VDC, set for steady tone.

Regulatory information


Manufacturer

Edwards, A Division of UTC Fire & Security

Americas Corporation, Inc.

8985 Town Center Parkway, Bradenton, FL

34202, USA

Year of

manufacture

The first two digits of the date code (located on

the product identification label) are the year of

manufacture.

UL

Regulated 24 DC and 24 FWR

North American

standards

UL 464

Contact information

For contact information, see www.edwardsutcfs.com.