Caution – Edwards Signaling 5553 Series User Manual
Page 5
1 5W 25V *
.9W 70V
1.8W 7 0V
0.48W 2 5V
7.5W 70V
15W 7 0V
7. 5W 25V *
1 .8W 25V
0.94 W 25V
3.8W 70 V
* DO NOT US E
FOR 70V
+
AUDIO IN PUT CONNECTION S
From Supervised
or Non Supervised
Amplifer
+
_
1/2" Conduit Entries
Power Tap
Selection Switch
(See table 1)
Note: To conform with UL requirements, wires must be connected as shown in wiring diagram.
To Next Speaker or
End-of-Line Resistor
Wire size; 18 Gauge minimum, 12 Gauge maximum.
+
_
Figure 4. Wiring Multiple 5553 Seres Speakers and/or supervised circuits
To ensure proper supervision of connection, do not use looped
wires under terminal screws. Break wire run. Use both sides
of terminal screws as shown.
U.S.
T 800-336-4206
F 800-454-2363
Canada
T 519 376 2430
F 519 376 7258
Asia
T 852 2907 8108
F 852 2142 5063
Australia
T 61 3 9259 4700
F 61 3 9259 4799
Europe
T 32 2 725 11 20
F 32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
www.edwardssignaling.com
CAUTION
Switch
Position
Impedance
25V
Line
SPL dB(A)
@ 10 ft.
70V
Line
SPL dB(A)
@ 10 ft.
1
5.0K
-
-
.9W
93
2
2.5K
-
-
1.8W
96
3
1.3K
.48W
91
3.8W
98
4
666
.94W
93
7.5W
101
5
333
1.8W
96
15.0W
103
6
89
7.5W
101
Do Not Use
on 70V
7
45
15.0W
103
Table 1. Power Tap Selector Switch
PAGE 4 P/N 3101297 ISSUE 02