Edwards Signaling E-RLY User Manual
Page 3
P/N 3101196 • REV 02 • ISS 28JAN13
3 / 4
Figure 3: Control relay function
(1) Normally closed contact (NC)
(2) Normally open contact (NO)
(3) Common contact
(4) Power-limited unless connected to a nonpower-limited source. If
the source is nonpower-limited, eliminate the power-limited mark
and maintain a minimum of 0.25 in. (6.4 mm) space from power-
limited wiring. For other mounting methods, see enclosure and
bracket installation sheets to maintain separation of power-
limited and nonpower-limited wiring. The wire size must be
capable of handling fault current from nonpower-limited source.
— or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending beyond
the jacket are separated by a minimum of 0.25 in. (6.4 mm)
space or by a nonconductive sleeve or nonconductive barrier
from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
(5) All wiring is power-limited and supervised
(6) Signaling line circuit (SLC) from previous device
(7) Signaling line circuit (SLC) to next device
(8) Not used
Figure 4: Polarity reversal relay function
(1) Normal
(2) Active
(3) Power out
(4) Power in
(5) Power-limited unless connected to a nonpower-limited source. If
the source is nonpower-limited, eliminate the power-limited mark
and maintain a minimum of 0.25 in. (6.4 mm) space from power-
limited wiring. For other mounting methods, see enclosure and
bracket installation sheets to maintain separation of power-
limited and nonpower-limited wiring. The wire size must be
capable of handling fault current from nonpower-limited source.
— or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending beyond
the jacket are separated by a minimum of 0.25 in. (6.4 mm)
space or by a nonconductive sleeve or nonconductive barrier
from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
(6) All wiring is power-limited and supervised
(7) Signaling line circuit (SLC) from previous device
(8) Signaling line circuit (SLC) to next device
TB2
TB1
(5)
(4)
(2)
(3)
(1)
(+)
( )
(6)
(7)
(8)
TB2
TB1
(6)
(5)
(2)
(1)
(+)
( )
(7)
(8)
(3)
(4)