Wiring – Edwards Signaling E-RLY User Manual
Page 2
2 / 4
P/N 3101196 • REV 02 • ISS 28JAN13
Figure 1: Module address
(1) Address switches
Figure 2: Module installation
(1) #4-24 × 1/2 self-tapping screw
(2) Wall plate
(3) Screw
(4) Module
(5) Compatible electrical box
Wiring
Wire in accordance with applicable requirements of the latest
editions of the local codes and standards and the local
authority having jurisdiction.
Note:
When stripping wire ends, exposing more wire may
cause a ground fault; exposing less wire may result in a faulty
connection.
Strip 1/4 in. (about 6 mm) from the ends of all wires that
connect to the terminal block of the module.
Notes
•
Only one conductor per terminal.
•
The signaling line circuit (SLC) circuit is power-limited and
supervised.
•
Refer to the panel documentation for SLC wiring
specifications.
To wire the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Make all wiring connections using Figure 3 or Figure 4
according to the desired function. Observe polarity of the
wires as shown in the diagrams.
(1)
(1)
(2)
(3)
(4)
(5)