Specifications – Edwards Signaling GCI Graphic Annunciator Interface Card User Manual
Page 3
P/N 3100973-ML • REV 2.0 • ISS 16MAR11
3 / 14
Figure 4: Remote key switch wiring
RKEY
Note:
Remove the jumper installed on EXTSW only if you are
installing a remote key switch.
Figure 5: Switch and LED wiring
LED+
LED+
SW-
SW-
LED+
SW–
+
SWxx
LEDxx
Switch and LED terminals are listed in Table 4 and Table 5.
Table 4: Switch terminal definitions
Terminal Description
J7-1 ACK/Silence
SW
J7-2 Reset
SW
J7-3
Signal Silence SW
J7-4 Drill
SW
J7-5
Lamp Test SW
J7-6 to J7-8
Not used
Terminal Description
J7-9 to J7-12
SW 1 to SW 4
J8-1 to J8-12
SW 5 to SW 16
Table 5: LED terminal definitions
Terminal Description
J1-1 Reset
LED
J1-2
Signal Silence LED
J1-3 Drill
LED
J1-4
Ground Fault LED
J1-5 Trouble
LED
J1-6 Controls
Enable
LED
J1-7 ACK/Silence
LED
J1-8
Lamp Test LED
J2-1 Power
LED
J2-2
Fire Alarm LED
J2-3 Supervisory
LED
J2-4 to J2-8
Not used
J3-1 to J3-8
LED 1 to LED 8
J4-1 to J4-8
LED 9 to LED 16
J5-1 to J5-8
LED 17 to LED 24
J6-1 to J6-8
LED 25 to LED 32
Specifications
Voltage 24
VDC
Current
Standby
Alarm
36 mA at 24 VDC
146 mA at 24 VDC
Switch inputs
Quantity
Type
5 dedicated, 21 total
Dry contact
Open collector outputs
Current
Power
factor
Quantity
Type
For LED driver use only
10 mA at 5.7 V input max.
PF 1.0 (resistive)
43
Common (11), zone or programmable (32)
LED current
7 mA at 5.7 VDC per LED, typical
Power wiring
14 to 18 AWG (1.0 to 2.5 mm²)
Annunciator circuit
Class/Style
Wire
size
Type
Length
Baud
rate
Class B, Redundant Class B, or Class A
18 to 14 AWG (1.0 to 2.5 mm²)
Twisted pair, 6 twists per ft. min.
4,000 ft. (1,219 m), max.
9600 to 115200 baud
Remote key switch
5 VDC at 1 mA, power-limited, unsupervised
Dimensions
3.25 Ч 10.25 Ч 1.50in. (8.3 Ч 2.6 Ч 3.8 cm)
Ground fault
impedance
0 Ω
Operating environment
Temperature
Relative
humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing