Specifications

Voltage

16 to 33 VDC and 16 to 33 VFWR

Strobe operating
current

See Table 3

Light output

Selectable at 95, 115, 150, and 177 cd

Sound level output

See Table 4

Default settings

Signal

Sound level

output

Strobe signal

output


Temporal
High dB
1 flash per second (fps)

Wire size

12 to 18 AWG (0.75 TO 2.50 mm²)

Compatible electrical
boxes

North American 4 in. square electrical box,
2-1/8 in. deep (no extension ring)

Operating environment

Temperature

Relative humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing

Regulatory information

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture

UL/ULC rating

Regulated 24 DC, regulated 24 FWR

This device was tested to the regulated
24 DC/FWR operating voltage limits of 16 V and
33 V. Do not apply 80% and 110% of these
values for system operation.

Environmental
class

UL: Indoor

Synchronization

Meets UL 1971 requirements. Maximum allowed
resistance between any two devices is 20

Ω.

Refer to specifications for the synchronization
control module, this strobe, and the control panel
to determine allowed wire resistance.

Agency listings

Meets ULC-S525. ULC-S526
UL 464, UL 1638, and UL 1971

Contact information