Table 3: Strobe operating current in RMS (A)

15 cd

30 cd

75 cd

95 cd

VDC

0.109

0.151

0.281

0.318

VFWR

0.131

0.194

0.379

0.437

VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified

Operating currents shown above were measured by UL at 16 VDC and
16 VFWR.

Table 4: Sound level output (dBA)

Wattage

25V (UL)

25V (ULC)

70V (UL)

70V (ULC)

1/4 W

80

78

80

81

1/2 W

84

81

84

81

1 W

87

87

87

87

2 W (UL)

90

91

2.2 W (ULC)

90

90

UL 1480: Sound level output at 10 ft (3.05 m) measured in a
reverberant room using 400 to 4,000 Hz band limited pink noise.

ULC-S541: Meets or exceeds 85 dBA in an anechoic chamber at 10 ft
(3.05 m).

Directional characteristics: Within 6 dB of on-axis sound level when
measured 90

° off-axis (horizontal).

Figure 6: Light output profile

Maintenance

This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.

Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.

Do no change the factory-applied finish.

Specifications

Operating voltage

Speaker

Strobe


25 VRMS (model S2) or 70 VRMS (model S7)
24 VDC, 24 VFWR

Supervisory voltage

30 V maximum

Strobe operating
current

See Table 3

Sound level output

See Table 4

Speaker response

400 to 4,000 Hz

Light output

Selectable at 15, 30, 75, and 95 cd

Default settings

1 flash per second (fps)

Wire size

12 to 18 AWG (0.75 TO 2.50 mm²)

Compatible electrical
boxes

North American 4 in. square electrical box,
2-1/8 in. deep (no extension ring)

Operating environment

Temperature

Relative humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing

Regulatory information

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture

UL/ULC rating

Regulated 24 DC and 24 FWR

This device was tested to the regulated
24 DC/FWR operating voltage limits of 16 V and
33 V. Do not apply 80% and 110% of these
values for system operation.

Environmental
class

UL: Indoor dry

Synchronization

Meets UL 1971 requirements. Maximum allowed
resistance between any two devices is 20

Ω.

Refer to specifications for the synchronization
control module, this strobe, and the control panel
to determine allowed wire resistance.

Agency listings

UL 1480, UL 1638 and UL 1971
CAN/ULC S526, ULC-S541,
BS EN 60065:2002 [1]

[1] Nameplate marking is located on the inside surface of the device.

0

20

40

60

80

100

120

140

160

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

130

135

140

145

150

155

160

165

170

175

180

185

190

195

200

205

210

215

220

225

230

235

240

245

250

255

260

265

270

275

280

285

290

295

300

305

310

315

320

325

330

335

340

345 350

355