P/N 3100560 • REV 5.0 • ISS 25AUG10

WARNING:

Electrocution hazard. To avoid personal injury or

death from electrocution, remove all sources of power and

allow stored energy to discharge before installing or removing

equipment.

Caution:

Electrical supervision requires breaking the wire run

at each terminal. Do not loop the signaling circuit field wires

around the terminals.

To install the horn-strobe:

1. Remove the cover by depressing both tabs on the top of

the unit with a small screwdriver and twisting slightly.

2. Set the horn signal, sound output level, and strobe signal

to the desired settings. See Figure 1.

To change the strobe to temporal (private mode), cut

from circle J1 to the edge of circuit board.

To change the horn signal from temporal to steady,

cut from circle J2 to the edge of circuit board.

To change the horn output level from high dB to low

dB, cut the J3 trace between the holes.

3. Slide the candela switch to the desired candela output by

aligning it with the indicator located left of the switch. See

Figure 2.

4. Connect the strobe terminals to the signal circuit field

wiring. You must observe polarity for the unit to function

properly. See Figure 3.

5. Mount the unit onto a compatible electrical box, making

sure not to overtighten the mounting screws.

6. Replace the cover by aligning it at the bottom, then

snapping it in at the top.

7. Test the unit for proper operation.

Figure 1: Horn and strobe settings

J2 J3

J1

1

2

3

1. J1: Strobe signal output

2. J2: Temporal/steady horn signal output

3. J3: dB sound output

Note: If the strobe is set to temporal (private mode), this device is no

longer UL 1971 listed and FM Approved but is UL 1638 listed.

Figure 2: Candela switch

110

75
30
15

Figure 3: Wiring diagram

1

2

-

+

1. From compatible fire alarm control panel

2. To next appliance, EOL, or return to source

Note: Polarity is shown in the alarm condition.

Maintenance

Caution:

To maintain the required agency listings, do not

change factory applied finishes.

This unit is not serviceable or repairable. Should the unit fail to

operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a

year or as directed by the local authority having jurisdiction.