Table 2: G1M-RM terminal connections
Terminal
Description
Terminal
Description
1
HORN IN +
5
STROBE IN +
2
HORN IN −
6
STROBE IN −
3
HORN OUT +
7
STROBE OUT +
4
HORN OUT -
8
STROBE OUT -
Specifications
Operating voltage
16 to 33 VDC; 16-33 VFWR
Output rating
3 A max. Actual value limited by
system NAC and power outputs
Synchronization
Flash
Resistance between two
appliances
1/s within 10 mss indefinitely
20 Ω max.
Wire size
12 to 18 AWG (0.75 to 2.50 mm²)
Electrical box
Compatible
Recommended
2-1/2 in. (64 mm) deep single-gang box
4 in. square box 1-1/2 in. (38 mm)
deep with single-gang trim ring
3-3/4 x 2 in. (95 x 51 mm) (H x W) or
greater
Operating environment
Temperature
Relative humidity
32 to 120 °F (0 to 49 °C)
0 to 93% noncondensing
Regulatory information
Manufacturer
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Year of
manufacture
The first two digits of the product serial number
(located on the product identification label) are
the year of manufacture.
UL rating
Regulated 24 DC, Regulated 24 FWR [1]
Environmental
class
UL: Indoor
North American
standards
UL 1971, UL 1638, UL 464, CAN/ULC S525,
CAN/ULC S526
[1] This module was tested to the regulated 24 VDC/FWR operating
voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these
values for system operation.
Contact information