Edwards Signaling 5530MHV User Manual
Page 5
P/N 3100006 • REV 4 • ISS 09AUG10
5 / 7
Catalog number
Voltage
Standby
current
Tone on
current
5530M-120N5
120 VAC 50/60 Hz
0.10 A
0.38 A
5530M-24Y6
125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz
0.10 A
0.02 A
0.10 A
0.10 A
0.20 A
0.10 A
0.32 A
0.20 A
5530M-120Y6
125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz
0.10 A
0.02 A
0.10 A
0.10 A
0.20 A
0.10 A
0.31 A
0.20 A
5530MHV-24AQ
24 VDC
24 VAC 50/60 Hz
0.10 A
0.10 A
1.5 A
2.3 A
5530MHV-24Y6
125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz
0.10 A
0.02 A
0.10 A
0.10 A
0.39 A
0.19 A
0.56 A
0.34 A
5530MHV-120Y6
125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz
0.10 A
0.02 A
0.10 A
0.10 A
0.40 A
0.20 A
0.62 A
0.37 A
Table 4: Dimensions
5530M
5530MHV
A
8 7/8” (225 mm)
11 1/2” (292 mm)
B
8 1/4” (210 mm)
9 3/4” (248 mm)
C
13” (330 mm)
14 1/4” (362 mm)
Table 5: PLC compatibility: PLC output to meet following product input parameters. Refer to Figure 10 and Figure 13.
Catalog number
Operating voltage
Max. off state leakage
current
Continuous on current
Surge (inrush/duration)
5530M-24AQ
24 VDC only
2 mA
740 mA
8 A / 4 mS
5530M-24N5
120 VAC 50/60 Hz
2 mA
360 mA
2.82 A / 4 mS
5530MHV-24AQ
24 VDC only
2 mA
1500 mA
8 A / 4 mS
5530M-120N5
120 VAC 50/60 Hz
5 mA
380 mA
2.82 A / 4 mS
Input board circuit
24 VDC
2 mA
6 mA
--
Table 6: Tone programming
Tone
SW 4-6 SW 4-5 SW 4-4 SW 4-3 SW
4-2 SW4-1 Description
Hex
No
Tone
OFF OFF OFF OFF OFF
OFF
00
Ding-Dong
OFF OFF OFF OFF OFF
ON Percussive pairs of 700 and 570 Hz tones, each
damped to 0
01
Warble
OFF
OFF
OFF
OFF
ON
OFF
575 and 770 Hz alternately, 87 ms each
02
Siren
OFF
OFF
OFF
OFF
ON
ON
600 – 1250 Hz up and down sweep in 8 s and repeat
03
Stutter
OFF OFF OFF ON OFF
OFF Percussive 470 Hz, 83 ms on, 109 ms off
04
Slow Whoop
OFF
OFF
OFF
ON
OFF
ON
600 – 1250 Hz upward sweep in 4 s and repeat
05
Beep
OFF
OFF
OFF
ON
ON
OFF
470 Hz, 0.55 s on, 0.55 s off
06
Chime 1
OFF
OFF
OFF
ON
ON
ON
700 Hz percussive repeat at 1 Hz
07
Fast Whoop
OFF
OFF
ON
OFF
OFF
OFF
600 – 1250 Hz upward in 1 s and repeat
08
Hi/Lo
OFF
OFF
ON
OFF
OFF
ON
780 to 600 Hz alternately, 0.52 s each
09
Rapid Siren
OFF
OFF
ON
OFF
ON
OFF
600 – 1250 Hz up and down sweep in 0.25 s and repeat
0A
Yeow
OFF
OFF
ON
OFF
ON
ON
1250 – 600 Hz downward sweep in 1.6 s and repeat
0B
Horn OFF
OFF
ON
ON
OFF
OFF
470 Hz continuous
0C
Air Horn
OFF
OFF
ON
ON
OFF
ON
370 Hz continuous
0D
Dual Tone
OFF
OFF
ON
ON
ON
OFF
470 – 500 Hz, 0.4 to 0.5 s cycle
0E
Chime 2
OFF
OFF
ON
ON
ON
ON
575 Hz percussive repeat at 1 Hz
0F
Westminster
OFF ON OFF OFF OFF
OFF Two
measures, 411 Hz, 520 Hz, 407 Hz, 312 Hz
10
Three Blind Mice
OFF
ON
OFF
OFF
OFF
ON
Four measures, 787 Hz, 714 Hz, 625 Hz, 952 Hz, 333
Hz
11
Phasor
OFF
ON
OFF
OFF
ON
OFF
416 – 625 Hz up and down sweep in 13 ms and repeat
12
Telephone
OFF
ON
OFF
OFF
ON
ON
570 and 770 Hz alternately, 50 ms each for 1.2s, 1.5s
delay and repeat
13
Staircase
OFF ON OFF ON OFF
OFF 440
–
2000 Hz up and down steps, 750 ms delay and
repeat
14