beautypg.com

Set serial id, Set range – Detcon PI-700 User Manual

Page 25

background image

Model PI-700

PI-700 Instruction Manual

Rev. 2.5

Page 21 of 54

When the AutoSpan value is between 101 and 1000, the adjustment increment is 50
When the AutoSpan value is between 1001 and 10000, the adjustment increment is 500

The menu item appears as: “Set AutoSpan Level”.

From the Set AutoSpan Level text scroll, hold the magnet over PGM1 or PGM2 until the “◄” prompt
appears and continue to hold the magnet in place for an additional 3-4 seconds (until the display starts to scroll
“Set Level”). The display will switch to “ XX“ (where XX is the current gas level). Swipe the magnet
momentarily over PGM2 to increase or PGM1 to decrease the AutoSpan Level until the correct level is
displayed. When the correct level is achieved, hold the magnet over PGM1 or PGM2 for 3-4 seconds to
accept the new value. The display will scroll “Level Saved”, and revert to “Set AutoSpan Level” text scroll.

Move to another menu item by executing a momentary hold, or return to Normal Operation via automatic
timeout of about 15 seconds (the display will scroll “Set AutoSpan Level” 4 times and then return to Normal
Operation).

3.5.3

Set Serial ID

Detcon Model PI-700 sensors can be polled serially via RS-485 Modbus™ RTU. Refer to Section 4.0 for
details on using the Modbus™ output feature.

Set Serial ID is used to set the Modbus™ serial ID address. It is adjustable from 01 to 256 in hexadecimal
format (01-FF hex). The current serial ID can be viewed in View Sensor Status using the instruction given in
Section 3.5.1 View Sensor Status.

The menu item appears as: “Set Serial ID”.

From the “Set Serial ID” text scroll, hold the programming magnet over PGM1 or PGM2 until the “◄”
prompt appears and continue to hold the magnet in place for an additional 3-4 seconds (until the display starts
to scroll “Set ID”). The display will then switch to “ XX“ (where XX is the current ID address). Swipe the
magnet momentarily over PGM2 to increase or PGM1 to decrease the hexadecimal number until the desired
ID is displayed. Hold the magnet over PGM1 or PGM2 for 3-4 seconds to accept the new value. The display
will scroll “ID Saved”, and revert to “Set Serial ID” text scroll.

Move to another menu item by executing a momentary hold, or, return to Normal Operation via automatic
timeout of about 15 seconds (the display will scroll “Set Serial ID” 5 times and then return to Normal
Operation).

3.5.4

Set Range

The full-scale range of a PI-700 sensor is determined at the time of order. The Intelligent Plug-in Sensor is
factory calibrated for this range. However, if the application requirements change and the user needs to alter
the original range, the “Set Range” function can be used to make field adjustments.

The currently selected full-scale range is displayed in the “View Sensor Status” menu. The factory calibrated
full-scale range is printed on the Intelligent Plug-in Sensor Label. When a new range is selected the 4-20mA
and Modbus™ outputs will automatically be rescaled, and the span gas level will default to 50% of the new
range.

The menu item appears as: “Set Range

From the “Set Range” text scroll, hold the programming magnet over PGM1 or PGM2 until the “◄” prompt
appears and continue to hold the magnet in place for an additional 3-4 seconds (until the display starts to scroll