2.3 Electrical characteristics

Selection of protection devices

UPS short-circuit current with inverter coupled and bypass AC source out of tolerances

When sizing the upstream circuit breakers, the parameters presented below must be taken into account.

Time/current curves for UPS input and output fuses

Sn

250 kVA

300 kVA

400 kVA

500 kVA

In (at 400 V)

361 A

433 A

577 A

721 A

Isc

1085 A

1085 A

1446 A

1975 A

Q1

Q4S

Q5N

NORMAL AC

BYPASS AC

Upstream
CB
(not supplied)

Downstream
CB
(not supplied)

output
fuses

input
fuses

Upstream
CB
(not supplied)

Load

10

4

10

3

10

2

10

1

10

-

1

10

-

2

10

-

3

10

-

4

10

4

10

3

10

2

10

I (A)

t (s)

400 kVA : 800A

500 kVA : 1000A

250-300 kVA : 630A