2000 kva, Connect the cables, Installation – APC GALAXY 7000 User Manual
Page 43
![background image](/manuals/36396/43/background.png)
Connecting the power cables > SSC maintenance cabinet
34020846EN/AD
- Page 43
1. Installation
2000 kVA
This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Key:
(1) Front face protective covers
(2) Roof protective covers
(3) Earth bar
(4) To Earth
(5) To the load
(6) To the SSC
(7) To the UPS
1 - Remove protective covers (1) and/
or (2).
Co n n e c t t h e c a b l e s
This operation may only be carried out by authorized staff.
See “Characteristics of the connection terminals”, page 21.
1 -Check switches Q3BP ext (1) and
Q5N ext (2) are in the OFF position as
shown opposite.
2 - Connect the protective conductor
(PE or PEN) to the earth bar
3 - Connect the UPS conductors in the
following order: L1, L2, L3
4 - Connect the AC Bypass
conductors in the following order: L1,
L2, L3
5 - Connect the load conductors in the
following order: L1, L2, L3
6 - Refit the protective covers