Ssc cabinet, 800 kva, Remove the protective covers – APC GALAXY 7000 User Manual

Page 33: Connecting the power cables, Installation

background image

Connecting the power cables >

34020846EN/AD

- Page 33

1. Installation

SSC cabinet

800 kVA

Re m o v e t h e p r o t e c t i v e c o v e r s

This operation must be carried out by qualified personnel.

The door must be opened using a Ronis 405 key.

Key

(1) Front protective covers
(2) Roof protective covers

(3) Earthing bar

(4) To the earth
(5) To the UPSs*

(6) To bypass AC line

(7) To the load

Connections through the top of the

UPS cabinets are possible using an
auxiliary cabinet 400 mm wide.

1. Remove the protective covers (1)
and/or (2).

*Or to the SSC maintenance cabinet,

See “SSC maintenance cabinet”,
page 42.

Co n n e c t i n g t h e p o w e r ca b l e s

This operation must be carried out by qualified personnel.

See “Characteristics of the connection terminals”, page 21.

1. Check that switches Q4S, Q3BP
and Q5N are in the OFF position as

shown opposite.

2. Connect the protective conductor

(PE or PEN) to the earth bar.

3. Connect the UPS conductors taking

care to respect the order, N**, L1, L2,

L3.

4. Connect the bypass AC conductors

taking care to respect the order, N**,
L1, L2, L3.

5. Connect the load conductors taking
care to respect the order, N**, L1, L2,

L3.

6. Connect the control-wire cables

(See “Connect the backfeed option”,

page 45.)

7. Put the protective covers back in

place.

** SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,

page 26.

A

A

5

7

6

1

1

2

2

3

4

OFF

OFF

OFF

5

6

7

Connection through the bottom

Right-hand view

Front view

Top view

Front

view

N L1 L2 L3

533

860

1060

533

Q5N

Q3BP

Q4S

N L1 L2 L3

OFF

OFF

OFF

N L1 L2 L3

UPSs

Bypass

Load

AC

Earth