500 kva, Remove the protective covers, Connecting the power cables – APC GALAXY 7000 User Manual

Page 28: Installation

background image

Connecting the power cables > Single or modular UPS cabinet

34020846EN/AD

- Page 28

1. Installation

500 kVA

R e m o v e t h e p r o t e c t i v e c o v e r s

This operation must be carried out by qualified personnel.

The door must be opened using a Ronis 405 key.

Key

(1) Protective covers
(2) Tie bar

(3) To normal AC line

(4) To the batteries
(5) To bypass AC line

(6) To the earth

(7) To the load
(8) Earthing bar

1. Remove the protective covers (1).

C o n n e c t i n g t h e p o we r c a b l e s

This operation must be carried out by qualified personnel.

See “Characteristics of the connection terminals”, page 21.

1. Check that switches Q1, Q4S,

Q3BP and Q5N are in the OFF

position as shown opposite.

2. Connect the protective conductor

(PE or PEN) to the earth bar.

3. Connect the normal AC conductors

taking care to respect the order, L1,
L2, L3.

4. Connect the bypass AC conductors
taking care to respect the order, N*,

L1, L2, L3.

5. Connect the load conductors taking

care to respect the order, N*, L1, L2,

L3.

6. Connect the battery.

7. Tie the cables down.

8. Connect the control-wire cables
(See “Connect the backfeed option”,

page 45.)

9. Put the protective covers back in

place.

* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.

Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.

2

8

1

4

5

7

3

6

8

360

260

390

+

-

N L1 L2 L3

N L1 L2 L3

L1 L2 L3

Q1

Q4S

Q3BP

Q5N

OFF

OFF

OFF

OFF

Normal AC

Bypass AC

Battery

Load

Earth