1. Installation

Ventilation

UPS cabinets

SSC cabinets

Pn = rated power, for other values please consult the after-sales support or the local office.

The optimum operating-temperature range is

20 to 25°C.

An operating temperature of 35°C is possible,

but battery life will be reduced.

Size the ventilation system taking into

account the values in the table below.

Power rating in kVA

250

300

400

500

Air flow (m³/h)

6000

6000

6000

8300

Heat losses to be
evacuated at Pn

kW

14.3

17.2

22.9

27.2

Cal./s

3418

4111

5473

6501

Power rating in kVA

800

1200

2000

Air flow (m³/h)

1000

Natural

Natural

Heat losses to be
evacuated at Pn

kW

3.7

< 1

< 1.5

Cal./s

884

< 240

< 360